You want a heat recovery VRF that carries large buildings, keeps design options open, and installs without drama. Toshiba’s SHRM-e was built for that brief. It’s a three-pipe system that delivers heating and cooling at the same time across many zones. It suits office towers, hotels, mixed-use blocks, and large refurbishments. It gives you long piping runs, strong seasonal performance, and a wide indoor unit choice.
You want a heat recovery VRF that carries large buildings, keeps design options open, and installs without drama. Toshiba’s SHRM-e was built for that brief. It’s a three-pipe system that delivers heating and cooling at the same time across many zones. It suits office towers, hotels, mixed-use blocks, and large refurbishments. It gives you long piping runs, strong seasonal performance, and a wide indoor unit choice. The numbers and claims below come from Toshiba’s own technical literature and recent data sheets. [1][2][3][4][5][6][7][8]
Explore our commercial air conditioning installation services:
https://www.climateworks.co.uk/commercial-air-conditioning
SHRM-e is Toshiba’s three-pipe heat recovery VRF on R410A. It moves heat from cooling zones to areas that need heating. That saves plant space and cuts the need for separate heating in many cases. It sits above standard two-pipe heat pump systems (where the whole network heats or cools at once) and beside newer R32 ranges aimed at lower charge and GWP. If your project needs long risers, many simultaneous zones, and stable seasonal performance, SHRM-e is in play. [1][2][4]
You can design for diverse uses on the same riser—meeting rooms, open plan floors, retail shells, and guest rooms—without separate plant. [1][2]
These examples are typical of the current SHRM-e portfolio and reflect the installed base seen in UK projects. Always confirm final selection with Toshiba’s selection tool for load profile, diversity, and line sizing. [4]
Keep the main riser simple and central. Use Y-branches and flow selector boxes in corridors or riser lobbies. Respect minimum straight lengths before and after fittings. Map total equivalent length to stay within the 1,000 m envelope. Check vertical steps floor-to-floor and keep indoor-to-indoor separation within limits (up to 40 m is cited in some regional guides). [1][2][3][4]
Toshiba allows high connected capacity ratios (see model notes and data book). In practice, many office floors run 100–130% connected load against outdoor nameplate. Use the office occupancy, solar gains, and after-hours loads to set diversity. [4][6]
Group indoor units with similar use. Example: perimeter offices with cassettes on one FS box, core meeting rooms with ducted units on another. That improves recovery between zones and reduces part-load cycling. [1][2]
TCC-Link supports local wired controllers, group controllers, and central touchscreens. BACnet/Modbus gateways feed BMS. Use dual set-point logic and timeclocks to avoid needless morning overshoots. [2][4]
Put SHRM-e outdoors on the roof or a screened terrace. Run a main riser through the core. Use ducted units over open plan areas and cassettes in collaboration spaces. Perimeter rooms get small ducted or wall units. Heat from the south side feeds north-side rooms in shoulder seasons. [1][2]
Each guest room gets a slim ducted unit for a clean finish and quiet fan speeds. Corridors and back-of-house zones sit on their own FS circuits. Heat from laundry and plant rooms can serve public areas in winter. [2]
Ground-floor retail uses cassettes and high static ducted for deep shops. Above, office plates use a mix of ducted and cassettes. Recovery between floors can be strong where trading hours differ. [1][3]
Each step maps back to the Toshiba spec PDFs and data book tables. [2][4][7][8]
SHRM-e is R410A, three-pipe heat recovery with long piping scope and a large installed base. SHRM Advance is R32, with a focus on lower refrigerant charge and NFC service tools. Both deliver simultaneous heating and cooling. Choose based on refrigerant policy, charge limits, and local spec. [1][3]
Depends on module size. Example: MMY-MAP0806FT8P-UK lists up to 18 indoor units; MMY-MAP1406FT8P-UK lists up to 31. Larger multi-module systems allow many more, within control and piping rules. Check the model sheet. [7][8]
Yes. Literature cites up to 90 m outdoor-to-indoor height difference, up to 1,000 m total piping, and generous furthest run limits. That covers most commercial towers without intermediate plant. [1][2][4]
Published sound data support rooftop use with screening and correct clearances. Low-noise modes and fan control help where façades are sensitive. Use antivibration pads on steel. [5]
Often no. Heat recovered from cooling zones can serve areas that need heating on the same system. Many projects still keep a small top-up heat source for edge cases. [1][2]
Leave safe routes to coil faces and control panels. Provide drain access for FS boxes in ceilings. Add hinged access panels for ducted units. Keep O&M labels on each circuit. [5]
Use the ESEER/SEER and SCOP values from the chosen module’s sheet. Many SHRM-e models show ESEER values above 8 on office profiles. Present these with the control strategy and expected run hours. [3][6][7]
Use F-Gas certified VRF teams with proven Toshiba experience. Commission to the manufacturer sequence and keep a full test record pack. That protects uptime and warranties. [2][4]
Scope: two floors, mixed meeting rooms and open plan.
Approach: one 14 HP set (MMY-MAP1406FT8P-UK) on the roof feeding two FS boxes. Ducted units over open plan; cassettes in rooms. Controls: dual set-point with timed setback. Result: strong seasonal performance and simple handover. [8]
Scope: 40 keys plus public areas.
Approach: multi-module stack to lift capacity. Slim ducted in rooms; cassettes in lobby and bar. Recovery from south-facing façade supports rooms on the shaded side during spring/autumn. Central controller for FM team.
Scope: retail ground floor; offices above.
Approach: separate FS circuits per use. Night set-back for offices; late trading hours for retail. Simple charge calc with a single riser keeps programme tight.
Send those, and we return a fixed quote with drawings, pipe routes, and a commissioning plan that fits your programme.
For tenders or design support on SHRM-e:
Commercial air conditioning installation
[1] Toshiba Air Conditioning UK — SHRM-e product page (piping limits and design scope).
https://www.toshiba-aircon.co.uk/product/shrme-3-pipe-heat-recovery-outdoor/
[2] Toshiba UK — SHRM-e standard specification (three-pipe VRF, components, design notes).
https://www.toshiba-aircon.co.uk/wp-content/uploads/2019/02/SHRMe-Specification-November-2017.pdf
[3] CDL/Toshiba — SHRM-e brochure and data (ESEER up to 8.17, system notes).
https://www.cdlweb.info/wp-content/uploads/2018/07/SHRMe-brochure-JFK.compressed.pdf
[4] Toshiba Klima (AT) — SHRM-e data sheets (pipe length up to 1,000 m, height 90 m, indoor count, 20 HP single module).
https://data.toshiba-klima.at/en/SHRM-e%20-%2090%2C40%20kW%20-%20R410A%20-%20VRF%20MMY-AP3216FT8P-E%20en.pdf
[5] Toshiba UK — SHRM-e outdoor dimensional/outline resources (clearances, access).
https://www.toshiba-aircon.co.uk/products/r410a-products/variable-refrigerant-flow-vrf-outdoor/3-pipe-heat-recovery-outdoor-unit/shrme-outdoor/
[6] Toshiba Aircondition EU pages — SHRM-e overview (ESEER up to 8.17, capacity bands, diversity).
https://www.toshiba-aircondition.com/en/air-conditioning-systems-for-companies/product-detail/shrme-50
[7] CDL — MMY-MAP0806FT8P-UK data sheet (8 HP capacities, ambient ranges, ESEER/SEER/SCOP).
https://www.cdlweb.info/wp-content/uploads/2024/11/Toshiba-VRF-Specification-CDL-FINAL-1_Part247-806f.pdf
[8] CDL — MMY-MAP1406FT8P-UK data sheet (14 HP capacities, indoor count, electrical data).
https://www.cdlweb.info/wp-content/uploads/2024/11/Toshiba-VRF-Specification-CDL-FINAL-1_Part250-1406.pdf
Dr. Julian Carter is a highly experienced thermal systems expert with over 15 years in the field, holding a PhD in thermal systems. His career spans academic research, consulting, and teaching, focusing on air conditioning and refrigeration systems. Dr. Carter bridges the gap between theoretical advancements and practical applications, providing expert insights to organisations like ClimateWorks, where his guidance informs decision-making and industry best practices. Notably, he has worked on international projects with organisations such as Daikin Industries, the International Institute of Refrigeration (IIR), and the United Nations Environment Programme (UNEP). These collaborations addressed energy efficiency, sustainable refrigerants, and advanced cooling technologies. Currently a lecturer at Edinburgh University, Dr. Carter combines his expertise with a passion for educating the next generation of engineers and advancing climate control technologies.